Simplex S4099-9006

Simplex 4099-9006 Double Action, Push Pull Down Fire Alarm Station

Samfura: S4099-9006

1. Gabatarwa

This manual provides comprehensive instructions for the installation, operation, and maintenance of the Simplex 4099-9006 Double Action, Push Pull Down Fire Alarm Station. This device is designed to initiate a fire alarm signal when manually activated, contributing to the overall safety and security of a building's occupants.

The Simplex 4099-9006 is an IDNet addressable manual pull station with an integrated LED indicator, ensuring reliable communication within compatible fire alarm systems.

2. Bayanin Tsaro

WARNING: Installation and servicing of this device must be performed by qualified personnel only, in accordance with all local and national electrical codes, and the National Fire Alarm and Signaling Code (NFPA 72).

  • Always disconnect power to the fire alarm control panel before installing or servicing the pull station.
  • Tabbatar da ƙasa mai kyau don hana girgiza wutar lantarki.
  • Do not paint over the pull station or obstruct its operation.
  • Test the pull station regularly as part of a comprehensive fire alarm system testing schedule.
  • This device is not intended for outdoor use unless specifically rated for such environments.

3. Samfurin Ya Ƙareview

The Simplex 4099-9006 is a robust, red-colored manual fire alarm pull station featuring a double-action mechanism (push then pull). It includes an integrated LED indicator for status feedback.

Simplex 4099-9006 Double Action Fire Alarm Pull Station with installation instructions

Figure 3.1: Simplex 4099-9006 Double Action Fire Alarm Pull Station. This image displays the front of the red pull station with "FIRE ALARM" and "PUSH PULL DOWN" labels, alongside a detailed instruction sheet for installation and mounting, and a small bag of mounting hardware.

Mabuɗin abubuwan haɗin gwiwa sun haɗa da:

  • Activation Handle: The "PUSH PULL DOWN" mechanism used to initiate an alarm.
  • Alamar LED: Provides visual status of the device (e.g., normal, alarm, trouble).
  • Toshe Tasha: For connecting to the fire alarm control panel's IDNet circuit.
  • Mounting Plate/Housing: Secures the device to a standard electrical box or surface.

4. Saita & Shigarwa

The Simplex 4099-9006 pull station can be installed using either single-gang or two-part mounting methods, typically on a standard 4-inch square electrical box (not supplied).

4.1 Pre-Ininstalling Checks

  • Verify that the fire alarm control panel is powered off.
  • Ensure the mounting location is clean, dry, and meets local code requirements for height and accessibility.
  • Confirm all necessary tools and hardware are available (e.g., screwdriver, wire strippers, mounting screws).

4.2 Hanyoyi na hawa

Refer to the installation diagrams provided with the product and shown in Figure 3.1 for visual guidance.

4.2.1 Single-Gang Mounting

  1. Secure the pull station directly to a standard single-gang electrical box.
  2. Ensure the device is flush with the wall surface.

4.2.2 Two-Part Mounting

  1. Install the backbox or mounting plate first, typically a 4-inch square electrical box.
  2. Mount the pull station assembly onto the installed backbox.
  3. This method may be used for flush trim or surface mounting applications.

4.3 Wayoyi

The 4099-9006 is an IDNet addressable device. Connect the pull station to the IDNet circuit of the fire alarm control panel using appropriate gauge wiring, following the wiring diagram provided on the device or in its specific installation sheet. Ensure polarity is correct.

  • Connect the incoming and outgoing IDNet circuit wires to the designated terminals.
  • Tabbatar cewa duk hanyoyin haɗin suna amintacce kuma ba su da guntun wando.

4.4 Bayan Shigarwa

  • Once installed and wired, restore power to the fire alarm control panel.
  • Verify the LED indicator on the pull station shows a normal operating status (typically a slow flash).
  • Perform a functional test of the pull station as described in the "Operating Instructions" section.

5. Umarnin Aiki

The Simplex 4099-9006 features a double-action activation mechanism to prevent accidental alarms.

5.1 Activating the Alarm

  1. TURA: Firmly push the "PUSH" bar located at the top of the activation handle.
  2. PULL DOWN: Once the "PUSH" bar is depressed, pull the handle "PULL DOWN" until it latches in the alarm position.
  3. Upon activation, the pull station will send an alarm signal to the fire alarm control panel, and the integrated LED will illuminate steadily (or change to a rapid flash, depending on system programming) to indicate an alarm state.

5.2 Resetting the Pull Station

To reset the pull station after an alarm, a special key (not included with this specific model, as indicated by "No Key" in the product title, implying a different reset mechanism or system-level reset) or tool is typically required to return the handle to its normal, non-alarm position. For the 4099-9006, the reset mechanism is internal and does not require a key. Simply push the handle back into its original position. The fire alarm control panel must also be reset to clear the alarm condition from the system.

6. Kulawa

Regular maintenance ensures the reliable operation of your Simplex 4099-9006 pull station. All maintenance should be performed by qualified personnel.

6.1 Dubawa na yau da kullun

  • Visual Inspection (Monthly): Check for any physical damage, obstructions, or signs of tampering. Ensure the pull station is clean and clearly visible.
  • LED Status (Monthly): Verify the LED indicator is showing a normal operating status (e.g., slow flash).

6.2 Functional Testing (Annually or as per local codes)

Functional testing should be conducted by a certified fire alarm technician.

  1. Notify building occupants and the monitoring station before testing.
  2. Activate the pull station as described in "Operating Instructions".
  3. Verify that the fire alarm control panel receives the alarm signal and initiates appropriate responses (e.g., sounding alarms, notifying monitoring station).
  4. Reset the pull station and the fire alarm control panel.
  5. Confirm the pull station returns to a normal operating state.

6.3 Tsaftacewa

Tsaftace wajen tashar ja da taushi, damp zane. Kada a yi amfani da masu tsabtace abrasive ko kaushi, saboda waɗannan na iya lalata ƙarshen ko abubuwan ciki.

7. Shirya matsala

This section addresses common issues you might encounter with the Simplex 4099-9006 pull station. For complex issues, contact a qualified fire alarm technician.

MatsalaDalili mai yiwuwaMagani
Pull Station does not activate alarm.Incorrect activation procedure; wiring issue; device fault; control panel issue.Ensure proper push-then-pull action. Check wiring connections. Verify control panel status. Contact technician if problem persists.
LED indicator is off or shows trouble.No power; wiring fault; device fault; control panel trouble.Check power to the control panel. Inspect wiring for breaks or shorts. Consult control panel manual for trouble codes. Contact technician.
Ƙararrawar ƙarya.Accidental activation; faulty device; wiring issue.Reset the pull station and control panel. Inspect for physical damage or obstructions. If recurring, contact technician.
Pull station handle does not reset.Internal mechanism issue; debris.Ensure no debris is obstructing the mechanism. Gently attempt to push the handle back. If it remains stuck, the unit may need replacement.

8. Ƙayyadaddun bayanai

SiffarDaki-daki
Lambar SamfuraS4099-9006
Nau'in SamfurDouble Action Manual Fire Alarm Pull Station
AlamarSimplex
Mai ƙiraSIMPLEX Grinnell
LauniJa
Hanyar kunnawaPush then Pull Down
Key Requirement for ResetNo Key Required (Internal Reset)
HaɗuwaIDNet Addressable
Haɗaɗɗun SifofiAlamar LED
Nauyin Abu0.5 Fam (kimanin oz 8)
Girman samfur6 x 6 x 4 inci (kimanin)
UPC643485653004
Kwanan Wata Farko AkwaiDisamba 21, 2015
Simplex 4099-9006 product packaging boxSimplex 4099-9006 product packaging box with PID and Part No.

Figure 8.1: Product packaging for the Simplex 4099-9006, showing the brown cardboard box with product identification labels. The labels confirm PID 4099-9006 and Part No. 06501211.

9. Garanti & Tallafi

9.1 Bayanin Garanti

This Simplex product is typically covered by a manufacturer's warranty against defects in materials and workmanship. Specific warranty terms and duration may vary. Please refer to the original purchase documentation or contact Simplex customer service for detailed warranty information.

Note: The product listing mentions "12 months warranty" and "30 days return if not satisfied". This information is from a third-party seller and may not reflect the official manufacturer's warranty. Always verify with the manufacturer.

9.2 Tallafin Fasaha

For technical assistance, installation guidance, or troubleshooting beyond the scope of this manual, please contact a certified fire alarm technician or the manufacturer directly.

Simplex Customer Support: Please visit the official SimplexGrinnell webshafin yanar gizo ko duba marufin samfurin ku don cikakkun bayanai game da hulɗa.

Don tambayoyi na gabaɗaya, zaku iya duba Simplex brand page on Amazon.

Takardu masu alaƙa - S4099-9006

Preview Simplex IDNet/MAPNET II Tashoshin Ƙararrawa na Wuta Mai Magana - Bayanan Samfur
Cikakkun bayanai kan Simplex 4099 Series da za a iya magance tashoshi na ƙararrawar wuta, masu jituwa tare da tsarin IDNet da tsarin MAPNET II. Fasaloli, ƙayyadaddun bayanai, zaɓuɓɓukan hawa, da zaɓin samfur don samfura daban-daban, gami da aiki ɗaya, mataki biyu (glass da turawa), da NO zaɓuɓɓukan GRIP. Mai yarda da buƙatun ADA kuma UL, ULC, FM, da CSFM suka jera su.
Preview Simplex Addressable Manual Stations: IDNet/MAPNET II Peripherals
Explore Simplex addressable manual fire alarm stations, detailing their features, single/double action types, NO GRIP options, and compatibility with IDNet/MAPNET II systems. Includes mounting and specification information.
Preview Simplex 2099 Series Single and Double Action Manual Fire Alarm Stations Datasheet
Datasheet for Simplex 2099 Series non-coded, non-addressable manual fire alarm pull stations. Covers features, operation types, application references, product selection, mounting options, and specifications.
Preview Simplex 4010ES: Tsarin umarni na kashewa ta atomatik zuba gicleurs
Jagorar dabara Simplex 4010ES détaillant da modules de commande zuba cikin tsarin kashewa ta atomatik para gicleurs, couvrant les modes déluge et preventif, avec specifications, homologations da schémas de câblage.
Preview Simplex 4004 Fire Alarm Control Panel: Installation and Operation Instructions
Comprehensive guide for installing, operating, and programming the Simplex 4004 Fire Alarm Control Panel (FACP), including system overview, requirements, wiring, module descriptions, and troubleshooting.
Preview Takardar Bayanan Sashen Kula da Gobara ta Simplex 4010ES: Tsarin Yaɗa Wuta ta atomatik, Ruwan Ruwa & Tsarin Tsaftacewa
Takardar bayanai ta fasaha don Sashen Kula da Gobara na Simplex 4010ES, wanda ke ba da cikakken bayani game da iyawarsa na sarrafa kashewa ta atomatik, ambaliyar ruwa, da kuma tsarin fesawa mai kariya.asing control. Ya haɗa da fasaloli, ƙayyadaddun bayanai, jerin hukumomi, da abubuwan da suka dace.