WATERLESS R-454B Smart Logic Controller

WATERLESS_-R-454B_-Smart_-Logic-Controller-PRODUCT

Disclaimer

  • Ingantacciyar shigarwa da sabis na Total Green Mfg. Heat Pump yana da mahimmanci don ingantaccen aikin sa. Dukkanin Tsarin Green Mfg. ƙwararrun ɗan kwangilar HVAC dole ne a girka kuma a yi masa hidima. Girman kayan aiki, zaɓi da shigarwa sune kawai alhakin mai sakawa.
  • Shigar da kayan aiki akan ƙirar madauki na ƙasan tagulla wanda bai dace da jimlar Green Mfg na yanzu ba. Dole ne a yi shigarwa daidai da umarnin da aka tsara a cikin wannan jagorar. Rashin samar da shigarwa ta ƙwararren ɗan kwangilar HVAC ta hanyar da ta dace da wannan jagorar zai ɓata kuma ya soke iyakataccen garanti na tsarin.
  • Jimlar Green Mfg. ba za ta kasance abin dogaro ga kowane lahani, aiki mara gamsarwa, lalacewa ko asara, kai tsaye ko na gaba, dangane da ƙira, ƙira, gini, aikace-aikace ko shigarwa na kowane fage da aka ƙayyade.
  • All Total Green Mfg. forced air units will have separate terminal strips labeled  “thermostat/zone board” and “air handler/furnace” for low voltage and are PLC  “controlled.
  • For proper equipment function, the thermostat or zone board must be tied to the  “thermostat/zone board terminal” strip. The air handler or furnace must be tied to the “air handler/furnace” terminal strip. There will also be additional terminal strips  for various functions based on the model type you may be working with. The information provided here is to supplement the installation manual specific to your unit.
  • IMPORTANT: For WGxA, WG2AH and WG2AD unit’s, if using a cased coil over a furnace, do NOT program your thermostat for dual fuel mode or, use the furnace settings. Leave the thermostat set to electric aux. heat, otherwise, you may interfere with proper PLC function. Follow the dual fuel function option for the unit model you are installing. This information is detailed in your unit installation manual. You will also want to check the aux. heat cycle rate (CPH) setting in the thermostat and set this to 1 or, the lowest available value depending on your thermostat brand and model.

WG1A Tilasta Iska Kawai- Jerin ayyuka

  1. The PLC checks that the LOW/HIGH pressure and discharge temperature switches are made. An open pressure switch input has a 60 second delay before setting a lockout and fault signal to  “X”. This is to prevent nuisance calls, especially at the beginning of the cooling season when the Earth Loops are at their coldest. “X” is set with any hard lockout condition. Turning the low voltage zuwa na'urar kwampreso a kashe sannan a sake kunnawa ta sake saita makullin muddin ba a buɗe majingin zazzabi ba. Maɓallin zafin fitarwa yana da maɓallin sake saiti na hannu. Buɗewar zazzabi mai buɗewa koyaushe zai buƙaci sake saitin hannu tare da ƙaramin voltage ikon sake zagayowar. Matsalolin matsa lamba suna atomatik.
  2. A “Y” call starts heating or cooling. A 20-minute timer will bring on AUX heat should that time elapse without having satisfied the heating call. Once aux. heat is called, aux. heat will stay called until the thermostat fully satisfies.
  3. Akwai mai shigar da jumper a filin tashar wayoyi mai alamar "A" da "S". Tare da shigar da jumper, naúrar za ta yi aiki tare da aux zafi tsiri kamar al'ada. Idan an cire jumper, PLC ta shiga cikin yanayin mai guda biyu yana dakatar da kwampreso lokacin da ake kira don aux zafi. Da zarar an gama kiran zafi aux, na'urar sanyaya na mintuna 5 na hana compressor sake kunnawa akan kiran “Y” har sai lokacin ya wuce. Wannan yana ba da lokaci don tanderu ya yi sanyi don haka iska mai zafi baya haifar da matsanancin fitarwa ko kullewa lokacin da kwampreso ya sake farawa.
  4. Lokacin da aka saita ma'aunin zafi da sanyio zuwa yanayin sanyaya, siginar "O" yana ƙarfafa bawul ɗin juyawa kuma yana kulle fitar da zafin aux.
  5. A ƙoƙarin rage yawan kuzari, PLC tana kashe wutar lantarki zuwa injin ƙararrawa lokacin da kwampreta ke gudana.
  6. This PLC program also allows the use of almost any heat/cool thermostat. Total Green Mfg. Strongly recommends using Honeywell 8000 series thermostats.
  7. If either the compressor unit or, the air handler/cased coil sensor detects a refrigerant leak, the unit will go into lockout mode disabling the compressor and backup heat source. The blower on forced air units will be activated and, the “LA” (Leak Alert) light along with the “X” (Lock Out) will turn on along with the “LA” terminal being energized with 24 volts AC. This terminal can be used as a trigger, if required by your local building codes, to set off a remote alarm and/or trigger a mechanical room exhaust fan in the event of a refrigerant leak.

WG2A Tilasta Iska Kawai- Jerin ayyuka

  1. The PLC checks that the LOW/HIGH pressure and discharge temperature switches are made. An open pressure switch input has a 60 second delay before setting a lockout and fault signal to“X”. During this 60 second time period, the compressor will only operate in 1st stage giving the system a chance to recover before setting a hard lock out. This is to prevent nuisance calls, especially at the beginning of the cooling season when the Earth Loops are at their coldest. “X” is set with any hard lockout condition. Turning the low voltage zuwa na'urar kwampreso a kashe sannan a sake kunnawa ta sake saita makullin muddin ba a buɗe majingin zazzabi ba. Maɓallin zafin fitarwa yana da maɓallin sake saiti na hannu. Buɗewar zazzabi mai buɗewa koyaushe zai buƙaci sake saitin hannu tare da ƙaramin voltage ikon sake zagayowar. Matsalolin matsa lamba suna atomatik.
  2. Kiran "Y1" yana farawa s 1sttage dumama ko sanyaya wanda zai ci gaba da minti 20 sannan lokaci zuwa 2nd stagya kamata wannan lokacin ya wuce ba tare da ma'aunin zafi da sanyio ya kira "Y2". Idan naúrar tana cikin yanayin dumama, sau ɗaya 2nd stage starts, a 20-minute timer will bring on AUX heat  should that time elapse without having satisfied the heating call. Once all stages an kira su, za a ci gaba da kiran su har sai thermostat ya cika sosai.
  3.  Idan fiye da kira na "Y1" sama da 3 a jere sun gudana ba tare da kiran thermostat na s 2nd batage cikin mintuna 20 ko, kafin minti 20 stage mai ƙidayar lokaci ya ƙare, a kira na huɗu “Y1”, an fara zagayowar kulawa wanda zai riƙe kuma ya kulle tsarin zuwa 2nd.tage   for 5 minutes to assure oil return to the compressor. If the system is air zoned, a Zone Override terminal “D” will energize to 24 volts. As described in your unit installation manual, this 24-volt signal can be used along with a field supplied isolation relay to call open the  largest zone and hold that damper open so the blower doesn’t see high static pressure during those 5 minutes. The maintenance cycle locks any other call out until completion. After the maintenance cycle, or if a “Y2” call is made before the maintenance cycle occurs, the
  4.  counter resets back to zero. This makes our system zone friendly as it allows for true 2 stages dumama da sanyaya.
    There is an installed jumper on the field wiring terminal block marked “A” and “S”. With the jumper installed, the unit will function with an aux heat strip as normal. If the jumper is removed, the PLC goes into dual fuel mode stopping the compressor when there is a
    call for aux heat. Once the aux heat call completes, a 5-minute cool down timer prevents the compressor from restarting on a “Y” call until the time elapses. This allows time for the furnace to cool so hot air doesn’t cause high discharge pressure or a lockout when the compressor restarts.
  5.  Lokacin da aka saita ma'aunin zafi da sanyio zuwa yanayin sanyaya, siginar "O" yana ƙarfafa bawul ɗin juyawa kuma yana kulle fitar da zafin aux.
  6. A ƙoƙarin rage yawan kuzari, PLC tana kashe wutar lantarki zuwa injin ƙararrawa lokacin da kwampreta ke gudana.
  7.  This PLC program also allows the use of almost any heat/cool thermostat. Total Green Mfg. Strongly recommends using Honeywell 8000 series thermostats.
  8. If either the compressor unit or, the air handler/cased coil sensor detects a refrigerant leak, the unit will go into lockout mode disabling the compressor and backup heat source. The blower on forced air units will be activated and, the “LA” (Leak Alert) light along with the “X” (Lock Out) will turn on along with the “LA” terminal being energized with 24 volts AC. This terminal can be used as a trigger, if required by your local building codes, to set off a remote alarm and/or trigger a mechanical room exhaust fan in the event of a refrigerant leak.

WG2AH Forced Air with Hydronic Heating Function

In addition to the function and features as described for WG2A units, The PLC program for the WG2AH units allows for switching priority call from forced air to hydronic heating as well as a  feature called “Split Zone” that are installer optioned by choosing jumper settings as described  below.

  1. Ana amfani da jumper a filin tasha na waya tsakanin tashoshin “R” da “AW” don ba da fifikon dumama iska akan dumama ruwa. Lokacin da aka cire wannan jumper, hydronic dumama ya zama fifikon kira.
  2. Rarraba Zone wani fasali ne wanda ke ba ku damar ƙona yanki ɗaya ko bene tare da zafin hydronic da wani yanki ko bene tare da iska mai tilastawa. Yankin Rarraba yana aiki ta hanyar cire fifikon mai tsallen kira a kan "R" da "AW" yana motsa shi a fadin "R" da "SZ" na shingen wayoyi na filin.
  3. Yayin da yake cikin yanayin "Split Zone", rukunin compressor zai ba da dumama iska mai ƙarfi zuwa yankin iska. Lokacin da tankin ajiya na buffer yayi kira don zafi, sashin compressor zai matsa zuwa ruwan zafi. Ya kamata a yi kira ga yankin iska yayin da na'urar kwampreso ke dumama ruwa, kiran yana tafiya kai tsaye zuwa tushen zafi aux don kula da yankin iska. Da zarar yawan zafin jiki na tanki ya cika, tsarin yana jujjuya zuwa dumama iska ta al'ada tare da na'urar kwampreso.
    1. When a hydronic heat call from the buffer tank takes place, the compressor turns off if it is running. 1 minute after that, the 3 way valve energizes and the SV1 valve de-energizes. 30 seconds after that stage, the water pumps starts to establish good water flow. 30 seconds after that stage, the compressor starts. Once the tank thermostat is satisfied, the compressor stops and the pump will continue to run for 30 seconds before turning off to gain any residual heat from the heat exchanger. 1 minute after the compressor stops, the 3-way valve de-energizes. 1 minute after that the compressor can restart for an air zone call. These timed cycles reduce system component wear by not having to shift under pressure or load.
  4. Ana kashe aikin dumama ruwa na Hydronic kowane lokacin da “O' terminal yana da kuzari yana sanya naúrar cikin yanayin sanyaya.
  5. If either the compressor unit or, the air handler/cased coil sensor detects a refrigerant leak, the unit will go into lockout mode disabling the compressor and backup heat source. The blower on forced air units will be activated and, the “LA” (Leak Alert) light along with the “X” (Lock Out) will turn on along with the “LA” terminal being energized with 24 volts AC. This terminal can be used as a trigger, if required by your local building codes, to set off a remote alarm and/or trigger a mechanical room exhaust fan in the event of a refrigerant leak.

WG2AD Tilasta Iska tare da Aikin Dumama Ruwa na Gida

Baya ga aiki da fasali kamar yadda aka bayyana ga raka'o'in WG2A kamar yadda aka bayyana a cikin sashe na farko na wannan takaddar, shirin PLC na rukunin WG2AD yana ba da damar sauya kiran fifiko daga iska mai tilastawa zuwa dumama ruwan gida.

  • Ana amfani da tsalle-tsalle a filin tasha na waya tsakanin tashoshi na “R” da “AW” don ba da fifikon dumama/ sanyaya iska akan dumama ruwan gida. Lokacin da aka cire wannan jumper, dumama ruwan gida ya zama kira mai fifiko.
  • When a water heating call from the water tank takes place, the compressor turns off if it is running. 1 minute after that, the 3 way valve energizes and the SV1 valve de-energizes. 30 seconds after that stage, the water pumps starts to establish good water flow. 30 seconds after that stage, the compressor starts. Once the tank thermostat is satisfied, the compressor stops and the pump will continue to run for 30 seconds before turning off to gain any residual heat from the heat exchanger. 1 minute after the compressor stops, the 3-way valve de-energizes. 1 minute after that the compressor can restart for an air zone call. These timed cycles reduce system component wear by not having to shift under pressure or load.
  • Ƙarin fasalin PLC mai aiki keɓanta ga ƙirar WG2AD wanda ke ba da damar dumama ruwa sama da digiri 120, shine ikon rukunin don kula da kwanciyar hankali na kwampreso ta hanyar murƙushe nauyin kwampreso kamar yadda ake buƙata don sarrafa matsa lamba.
  • If either the compressor unit or, the air handler/cased coil sensor detects a refrigerant leak, the unit will go into lockout mode disabling the compressor and backup heat source. The blower on forced air units will be activated and, the “LA” (Leak Alert) light along with the “X” (Lock Out) will turn on along with the “LA” terminal being energized with 24 volts AC. This terminal can be used as a trigger, if required by your local building codes, to set off a remote alarm and/or trigger a mechanical room exhaust fan in the event of a  refrigerant leak.

Smart Logic Controller
WG1H 100% Ruwa mai zafi da ruwan sanyi kawai - Jerin ayyuka

  1. PLC yana bincika cewa an yi matsi mai KYAU / HIGH, HX Low da Matsalolin zafin jiki. Buɗewar shigar da canjin aminci yana da jinkiri na daƙiƙa 60 kafin saita kulle kulle da siginar kuskure zuwa "X". Wannan shi ne don hana kiran da ba a so, musamman a farkon lokacin sanyi lokacin da madaukai na duniya suka kasance mafi sanyi. An saita “X” tare da kowane yanayin kullewa mai wuya. Juya ƙananan voltage zuwa na'urar kwampreso a kashe sannan a sake kunnawa ta sake saita makullin muddin ba a buɗe majingin zazzabi ba. Maɓallin zafin fitarwa yana da maɓallin sake saiti na hannu. Buɗewar zazzabi mai buɗewa koyaushe zai buƙaci sake saitin hannu tare da ƙaramin voltage ikon sake zagayowar. Matsakaicin matsi da HX Ƙananan madaidaicin zafin jiki suna atomatik.
  2. Kiran "N" yana fara famfo mai da'ira na tsawon daƙiƙa 30 kafin compressor don ba da damar cikakken kwarara ta cikin HX (mai musayar zafi) kafin fara kwampreso. Da zarar an gama kiran, famfon zai yi ƙarin daƙiƙa 30 bayan damfara ya tsaya don share HX na kowane saura zafi. Wannan yana faruwa ba tare da la'akari da kiran ruwa mai zafi ko sanyi ba.
  3. If the compressor unit sensor detects a refrigerant leak, the unit will go into lockout mode disabling the compressor. The “LA” (Leak Alert) light along with the “X” (Lock Out) will turn on along with the “LA” terminal being energized with 24 volts AC. This terminal can be used as a trigger, if required by your local building codes, to set off a remote alarm and/or trigger a mechanical room exhaust fan in the event of a refrigerant leak.

Idan kuna da wasu tambayoyi game da ɗayan waɗannan ayyukan, tuntuɓi Total Green Mfg. a 419-678-2032 don goyon bayan fasaha.

Tambayoyin da ake yawan yi

  • Q: Can I use any thermostat with the Smart Logic Controller?
    A: Yes, the PLC program allows for the use of almost any heat/cool thermostat, but Total Green Mfg. recommends using  Honeywell 8000 series thermostats for optimal performance.